HomeProductsHeat Transfer Fluid
Back to Products

Heat Transfer Fluid Industrial Heat Transfer and Antifreeze Fluids

Heat transfer fluids are dual-function chemicals that both prevent freezing and protect the system's metal components against corrosion in closed-circuit heating, cooling and heat pump systems. Akem Kimya's METOX Antifrozen family consists of products built on two different bases and manufactured under a DIN EN ISO 9001 quality system. Monoethylene glycol (MEG)-based METOX Antifrozen (N) is a highly efficient, economical solution for industrial cooling, heat pumps, heat recovery systems and leak detection applications. In plants where there is a risk of contact with food or beverages (breweries, dairies, ice cream factories, cold stores), the non-toxic, propylene glycol (MPG)-based METOX Antifrozen (L) is preferred — this product is also approved as an antifreeze filling fluid for sprinkler fire-extinguishing systems. METOX Antifrozen Solar, developed specifically for solar energy systems, is formulated for solar thermal applications that require high-temperature resistance. All three products are manufactured with a corrosion inhibitor package that is free of nitrites, amines, borates, silicates and phosphates and formulated without carcinogenic/mutagenic/reprotoxic (CMR) substances, and they are continuously tested to ASTM D 1384.

Key Features

  • Heat transfer
  • Corrosion prevention

METOX ANTIFROZEN is a family of glycol-based industrial antifreezes and heat transfer fluids. It consists of three products: N (monoethylene glycol) for industrial systems, L (monopropylene glycol) for the food and pharmaceutical sector, and SOLAR (propylene glycol with high-temperature stability) for solar energy systems.

A heat transfer fluid has two functions, and both work at the same time:

The first is to carry heat. In a closed-circuit cooling or heating system, the fluid picks up heat from the source and carries it to the heat exchanger. Water does this too — in fact, water's heat-carrying capacity is higher than that of glycol.

The second is to protect the system. Water freezes at 0 °C, and when it freezes it expands and bursts pipes, heat exchangers and pumps. Water also causes corrosion and scale on metal surfaces. A glycol-based heat transfer fluid lowers the freezing point, raises the boiling point and stops corrosion with its inhibitor package.

Choosing the right product means striking a balance between these two functions: as the glycol ratio rises, freeze protection increases but heat transfer efficiency falls somewhat. Targeting more freeze protection than the system actually needs means both unnecessary cost and an unnecessary loss of efficiency.

MEG and MPG compared

Industrial antifreezes have two basic raw materials, and the choice is made almost entirely on the basis of contact risk.

CriterionMEG — Monoethylene GlycolMPG — Monopropylene Glycol
Akem productMETOX ANTIFROZEN NMETOX ANTIFROZEN L / SOLAR
ToxicityToxic. Causes serious poisoning if swallowedLow toxicity. Raw material suitable for food-contact applications
Food / drinking water systemsCannot be usedCan be used
Heat transfer efficiencyHighHigh (somewhat lower than MEG)
ViscosityLower — less pump loadHigher, especially at low temperatures
Ratio required for the same freezing pointLowerSomewhat higher
CostLowerHigher
Typical useClosed-circuit industrial cooling, HVAC, chillersFood, beverages, pharmaceuticals, solar energy, lines with a contact risk

The decision rule in one sentence: if, in the event of a leak, the fluid could come into contact with food, drinking water or people, choose MPG; otherwise, MEG.

The cost difference is real, but this is not the place to save money. Using MEG in a food plant means a product recall and a production stoppage after a single heat exchanger leak.

Concentration and freeze protection

METOX ANTIFROZEN N is used mixed with water. When preparing the mixture, use soft water or purified water instead of mains water — the calcium and magnesium in mains water react with the inhibitor package and form a precipitate.

% METOX ANTIFROZEN N in water (by volume)Freezing point (ASTM D 1177)
%20 V/V−9 °C
%25 V/V−12 °C
%30 V/V−16 °C
%35 V/V−20 °C
%40 V/V−25 °C
%45 V/V−31 °C
%50 V/V−37 °C
%55 V/V−45 °C
%60 V/V−53 °C

How do you choose the ratio? Take the lowest temperature recorded in the system's region over the last 10 years and add a 5–10 °C safety margin. For example, if the region's minimum temperature is −15 °C, the target freezing point is between −20 and −25 °C; a ratio of 35–40% is selected from the table.

Why shouldn't a higher ratio than necessary be used? As the glycol ratio rises, viscosity increases, pump load rises and specific heat capacity falls. Mixtures above 60% do not increase freeze protection — on the contrary, the freezing point of pure glycol is higher than that of a water-glycol mixture.

For METOX ANTIFROZEN L, the mixing ratio is set within the 25%–50% range using the same logic.

Corrosion prevention and ASTM D 1384

What determines the service life of a heat transfer fluid is not the glycol but the inhibitor package. Glycol prevents freezing; what keeps the system going is the corrosion inhibitors.

Five different metals can be present at the same time in a closed-circuit system: copper pipes, brass fittings, steel housings, soldered joints and aluminium heat exchangers. When these metals are in contact with each other and there is a conductive fluid between them, galvanic corrosion begins. The inhibitor package stops this mechanism by forming a protective film on every metal surface.

ASTM D 1384 is the standard test method that measures the corrosion behaviour of heat transfer fluids in glassware. The test keeps six different metal coupons (copper, solder, brass, steel, cast iron, cast aluminium) immersed in the fluid at 88 °C for 336 hours and measures the weight loss of each coupon. The result shows numerically how compatible the fluid is with each metal.

This is the first document to look at when evaluating a heat transfer fluid. Organisations preparing technical specifications should request the ASTM D 1384 test report.

ASTM D 1384 test results and safety data sheets (MSDS) for METOX ANTIFROZEN N and L are provided on request.

System maintenance

A heat transfer fluid is not a "fill and forget" consumable. The inhibitor package is depleted over time, and once it is depleted the fluid stops protecting — the glycol is still there, but the system is no longer protected.

CheckIntervalWhat to do
pH measurementOnce a yearIf the value is falling, the inhibitor package is being depleted — plan a fluid change
Mixing ratio (refractometer)Once a year, before winterIf water has been topped up, the ratio may have dropped; recalculate freeze protection
Visual checkOnce a yearCloudiness, sediment or a change of colour are signs of deterioration
Fluid changeDepending on the system and operating conditionsThe fluid is drained completely, the system is flushed and a new mixture is filled

Common mistake: adding only water to the system when the level drops. This lowers both freeze protection and inhibitor concentration. Topping up should be done with a mixture of the same ratio.

Second common mistake: mixing fluids of different brands with different inhibitor technologies. Inhibitor packages can react with each other and form a precipitate. If you are changing brands, the system must be drained completely and flushed.

Quick Action

Request a quote now to get detailed information, request technical specifications or place an order for this product.

Product Category

Technical Documents

You can request MSDS and TDS documents from our technical documents page.

Heat Transfer Fluid — Frequently Asked Questions

MEG (ethylene glycol) is toxic; it is used in closed-circuit industrial systems. MPG (propylene glycol) has low toxicity; it is used in systems where there is a risk of contact with food, beverages, pharmaceuticals or drinking water. If there is a possibility of contact with food or people in the event of a leak, MPG is chosen.

METOX ANTIFROZEN N for industrial cooling, HVAC, chillers, railway systems and wind turbines. METOX ANTIFROZEN L for food, beverage and pharmaceutical plants and communal buildings. METOX ANTIFROZEN SOLAR for solar hot water systems.

Add a 5–10 °C safety margin to the lowest temperature in your region and choose the ratio from the concentration table. Example: 35–40% V/V for a region with a minimum of −15 °C.

Do not use it. The calcium and magnesium in mains water react with the inhibitor package and form a precipitate. Use soft water or purified water.

Check the pH and mixing ratio once a year. If the pH is falling or there is cloudiness/sediment, it is time for a change. METOX ANTIFROZEN SOLAR has a longer change interval owing to its resistance to thermal shock.

Do not mix them. Different inhibitor technologies can react with each other and form a precipitate. When changing brands, the system should be drained and flushed.

No. The N product is ethylene glycol-based and toxic; it must never be used in food, beverage or drinking water systems. Use METOX ANTIFROZEN L for these applications.

It should not be used. During stagnation, the collector temperature rises above 200 °C; at this temperature standard antifreeze turns tarry and clogs the pipes. METOX ANTIFROZEN SOLAR eliminates this problem with its reversible evaporation property.

25 kg jerrycan · 30 kg jerrycan · 1,000 kg IBC tank

N and L are concentrates; they are used diluted with water. SOLAR is available both as a concentrate and as a ready-to-use pre-mix; the concentrate is diluted with water, while the ready-to-use pre-mix is used without dilution.

All three products are available in 25 kg and 30 kg jerrycans and 1,000 kg IBC tanks.